Access Control : How to RESET control unit with SW1 & SW2 buttons ?

Modificato il Thu, 30 Dec 2021 alle 03:27 PM






SW1 to erase memory of the control unit :

- Power off the control Unit.  

- Hold SW1 Swtich while restoring Power.  

- Wait for the blue LED on the expansion bus to light up (approximately 10 seconds) while holding the switch down.

- Release SW1




SW2 to restore factory network settings (IP address : 192.168.2.150, mask 255.255.255.0). 

- Power off the control Unit.   

- Keep the switch pressed while turning the power back on.



Remark 


- To configure the control unit with a fixed IP address, release the switch at the first flash of the extension bus LED (about 5 seconds).

To configure the control unit in DHCP mode, wait for the second flash of the extension bus LED (approximately 5 seconds after the first flash).

Release SW2 

Questo articolo ti è stato utile?

Fantastico!

Grazie per il tuo feedback

Siamo spiacenti di non poterti essere di aiuto

Grazie per il tuo feedback

Facci sapere come possiamo migliorare questo articolo!

Seleziona almeno uno dei motivi
La verifica CAPTCHA è richiesta.

Feedback inviato

Apprezziamo il tuo sforzo e cercheremo di correggere l’articolo